Page view 43
34
Connecting the AC power supply to a power strip
with lightning protection
CAUTION:
Make sure the PE terminal of the power socket has been securely grounded.
If part of the AC power line is routed outdoors, use a power strip with lightning protection to connect the
AC power cord of the firewall to the AC power line to protect the firewall from being damaged by
lightning strikes.
You can attach the power strip to the rack, workbench, or wall of equipment room.
After you connect the AC power cord from the firewall to a socket on the power strip, verify that the green
RUN LED on the strip is on and the red LED is off.
If the red LED is on, use a multimeter to check the polarity of the wires in the power socket for wrong
connections. If the zero wire (left) and the live wire (right) are correctly connected, check for missing
grounding connection.
Figure 30 Power strip with lightning protection
(1) Operating LED (green) On means the circuit is operating correctly.
Off means the circuit is dama
g
ed.
(2) Grounding/pole detection LED
(red)
On indicates a wrong wire connection (the wire is not grounded or the live
line and null line are reversely connected), and you need to check the
power supply line.
(3) Power switch
(4) IEC standard socket It is used to connect to the power supply in the equipment room through a
power cord.
(5) Overload automatic protector The protector automatically opens the electric circuit when the current
exceeds the threshold and closes the electric circuit when the current drops
below the threshold.
(6) Multifunctional socket It is used to connect the power supply of the firewall.
6
NNNN
L
LL L
1 2 3
4
5